Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEUTRAL CANNOT BE SMALLER THAN FEED #8 WIRE MAX 50 AMP TO SUB-PANEL NEED SEPARATE GROUNDING BAR AND ISOLATED NEUTRAL BAR ON SUB-PANEL NEED LISTED FIXTURE OVER SHOWER EXPOSED LAMPS NOT PERMITTED IN CLOSET HAVE COVERS ON ALL DEVICES STOPPED INSPECTION |
|
| 07/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |