Permit: T07CM01824

Parcel: 14117014B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/20/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/17/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- EXHAUST FANS NOT INTERLOCKED CORRECTLY
- LIGHT SWITCH SHOULD TURN ON EXHAUST FAN 1ST THEN EXHAUST FAN SHOULD TURN ON HEAT PUMP FAN MOTOR
- CONDENSATE TRAPS INSTALLED BACKWARDS
- AIR BALANCE OK
03/12/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- EXHAUST FANS NOT INTERLOCKED WITH AC UNITS
AS PER PLANS
- PROVIDE CONDENSATE DRAINS ON ROOF
- PROVIDE AIR BALANCE REPORT
02/07/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED