Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
|
| 12/05/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - VAPOR BARRIERS NOT SEALED PER DETAIL ON PLANS. - UNLISTED DUCT TAPE WAS USED. - SOME DUCTS NOT SIZED PER PLANS & SOME REDUCED AT REGISTER BOX - DIFFUSERS NOT INSTALLED PER DETAILS - PROVIDE PERMISSION FROM ENGINEER IF CHANGING ANYTHING - PROVIDE CLEANOUT TEES IN CONDENSATE PIPING - OK TO INSULATE CONDENSATE PIPING |