Permit: T07CM01824

Parcel: 14117014B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/13/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
12/05/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- VAPOR BARRIERS NOT SEALED PER DETAIL ON PLANS.
- UNLISTED DUCT TAPE WAS USED.
- SOME DUCTS NOT SIZED PER PLANS & SOME REDUCED AT REGISTER BOX
- DIFFUSERS NOT INSTALLED PER DETAILS
- PROVIDE PERMISSION FROM ENGINEER IF CHANGING ANYTHING
- PROVIDE CLEANOUT TEES IN CONDENSATE PIPING
- OK TO INSULATE CONDENSATE PIPING