Permit: T07CM01821

Parcel: 13609014B


Addresses:

10355 E 29TH ST 02


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01821

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/24/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ITEMS 5, 10 AND 11 FROM INSPECTION ON 9/18/07
09/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PROPER SIZE FUSES FOR HP-1 & HP-2
2. LABEL DISCONNECTS & HEAT PUMPS/AC UNITS
3. INSTALL PROTECTIVE BUSHINGS ON FEED TO SUB-PANEL
4. NOT ALL LIGHT FIXTURES WORKING
5. LABEL CIRCUITS IN PANELS
6. AC 3 NAMEPLATE DOES NOT INDICATE BREAKER/FUSE SIZE
7. CANNOT SEE BREAKER/FUSES SIZE ON NAME PLATE FOR AIR HANDLERS
8. MARK ACCESSORIES ON AIR HANDLERS
9. CHECK EM LIGHTING TIED INTO LIGHTING CIRCUITS
10. MISSING EM LIGHTS/NOT PER PLANS
11. WIRE PROJECTION SCREEN