Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01821
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ITEMS 5, 10 AND 11 FROM INSPECTION ON 9/18/07 |
|
09/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL PROPER SIZE FUSES FOR HP-1 & HP-2 2. LABEL DISCONNECTS & HEAT PUMPS/AC UNITS 3. INSTALL PROTECTIVE BUSHINGS ON FEED TO SUB-PANEL 4. NOT ALL LIGHT FIXTURES WORKING 5. LABEL CIRCUITS IN PANELS 6. AC 3 NAMEPLATE DOES NOT INDICATE BREAKER/FUSE SIZE 7. CANNOT SEE BREAKER/FUSES SIZE ON NAME PLATE FOR AIR HANDLERS 8. MARK ACCESSORIES ON AIR HANDLERS 9. CHECK EM LIGHTING TIED INTO LIGHTING CIRCUITS 10. MISSING EM LIGHTS/NOT PER PLANS 11. WIRE PROJECTION SCREEN |