Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01821
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/05/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL 2 TWIN LUGS IN XFMR ON GROUND & NEUTRAL (XO) AND INSTALL #4 JUMPER BETWEEN XO & GROUND 2. CONNECT #4 BONDING JUMPER TO DISCONNECT ENCLOSURE 3. IDENTIFY 277V/480V CONDUCTORS AT XFMR 4. WILL CHECK THESE ITEMS AT FINAL |
|
08/30/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING JUMPER FROM XFMR TO DISCONNECT TO BE SIZED #4 PER NEC 250.30(A)(5) 2. INSTALL BONDING JUMPER IN XFMR FROM XO TO GROUND PER NEC 250.30 (A)(1) SIZE TO BE #4 3. CONNECT GROUNDING ELECTRODE CONDUCTOR TO XFMR 4. SEPARATE GROUNDS & NEUTRALS AT SECONDARY DISCONNECT AT XFMR 5. PROPERLY GROUND AC DISCONNECTS CANNOT USE SELF-TAPPING SCREWS. |
|
08/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL WALL 2. OK RACEWAY TO TRANSFORMER |
|
08/15/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. RACEWAY FROM SES TO X-FMR TO BE METALLICLY CONTINUOUS 2. PROVIDE INSTALLATION INSTRUCTIONS FOR HID FIXTURE BASELITE CORP ISSUE NO. A-151, 153 3. STILL NEED ANSWER ON FLOOR BOX LISTING |
|
08/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. STILL NEED ANSWER ON FLOOR BOX LISTING 2. NEED TO PROVIDE INSTALLATION INSTRUCTIONS FOR LIGHT FIXTURES WITH REMOTE BALLASTS. 3. OK EMT INSTALLATION ON OPEN CEILING AREA |
|
07/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK SOFFIT AT BACK DOOR 2. OK EMT & LIGHT BOXES IN OPEN AREA 3. FLOOR BOXES TO BE LISTED FOR THE USE. PLEASE PROVIDE LISTING ON BOXES USED. |
|
07/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS STORAGE ROOM & SOUND LIGHTING/CONTROL AREA 2. PROVIDE REVISED & APPROVED SET OF DRAWINGS 3. INSTALL GROUND TAILS IN METAL BOXES |