Permit: T07CM01821

Parcel: 13609014B


Addresses:

10355 E 29TH ST 02

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/20/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL 2 TWIN LUGS IN XFMR ON GROUND & NEUTRAL (XO) AND INSTALL #4 JUMPER BETWEEN XO & GROUND
2. CONNECT #4 BONDING JUMPER TO DISCONNECT ENCLOSURE
3. IDENTIFY 277V/480V CONDUCTORS AT XFMR
4. WILL CHECK THESE ITEMS AT FINAL
08/30/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BONDING JUMPER FROM XFMR TO DISCONNECT TO BE
SIZED #4 PER NEC 250.30(A)(5)
2. INSTALL BONDING JUMPER IN XFMR FROM XO TO GROUND PER NEC 250.30 (A)(1) SIZE TO BE #4
3. CONNECT GROUNDING ELECTRODE CONDUCTOR TO XFMR
4. SEPARATE GROUNDS & NEUTRALS AT SECONDARY DISCONNECT AT XFMR
5. PROPERLY GROUND AC DISCONNECTS CANNOT USE SELF-TAPPING SCREWS.
08/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL WALL
2. OK RACEWAY TO TRANSFORMER
08/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. RACEWAY FROM SES TO X-FMR TO BE METALLICLY CONTINUOUS
2. PROVIDE INSTALLATION INSTRUCTIONS FOR HID FIXTURE BASELITE CORP ISSUE NO. A-151, 153
3. STILL NEED ANSWER ON FLOOR BOX LISTING
08/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. STILL NEED ANSWER ON FLOOR BOX LISTING
2. NEED TO PROVIDE INSTALLATION INSTRUCTIONS FOR LIGHT FIXTURES WITH REMOTE BALLASTS.
3. OK EMT INSTALLATION ON OPEN CEILING AREA
07/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK SOFFIT AT BACK DOOR
2. OK EMT & LIGHT BOXES IN OPEN AREA
3. FLOOR BOXES TO BE LISTED FOR THE USE. PLEASE PROVIDE LISTING ON BOXES USED.
07/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS STORAGE ROOM &
SOUND LIGHTING/CONTROL AREA
2. PROVIDE REVISED & APPROVED SET OF DRAWINGS
3. INSTALL GROUND TAILS IN METAL BOXES