Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK GYM & COMPUTER LABS 1. WAITING FOR PLAN REVISIONS |
|
| 09/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK DWELLING UNITS ONLY 1. #297 - OUTSIDE CEILING LIGHTS MISSING 2. NO MORE THAN 360 DEG. IN A CONDUIT RUN 3. ATTACH FIXTURES TO GRID 410.16 - 2 SUPPORT WIRES IN OPPOSITE COVERS ARE NEEDED 4. INDEPENDENTLY SUPPORT ELECTRIC ABOVE CEILING 300.11 AND USE APPROVED METHODS 5. CORRECTLY INSTALL COVERS 6. CLEAN EXCESS FOREIGN MATERIAL FROM PANEL 7. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 8. TIGHTEN LOOSE FITTINGS 9. NEED PERMANENT LABELING AT MAIN SWITCHBOARD. |
|
| 09/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* BOXES MORE THAN 1/4" AT NON-COMBUSTIBLES AND FLUSH AT COMBUSTIBLE TO USE APPROVED EXTENDER RINGS 314.20 RECEIVED CHECK #1989 FOR $108.00 |
|
| 08/31/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ACCURATE AS BUILT REQUIRED BEFORE FINAL 2. PROPER PROTECTION REQUIRED FOR SUPPLIED EQUIPMENT (TV EXTENSION) 3. INSTALL ARC SHIELDS AT OUTLETS AND/OR P-RINGS AS REQUIRED. |
|
| 08/31/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLANS TO BE REFLECTIVE OF PANEL WIRING BEFORE FINAL (ACCURATE AS BUILT) 2. NO 2 WIRE ZIP CORD EXTENSION CORDS -- ALL MUST BE 3-WIRE GROUNDED - PROVIDE PROPER PROTECTION WITH LISTED ADAPTORS 3. BOXES IN COMBUSTIBLES TO BE FLUSH WITH SURFACE 314.20 OR 1/4" IN NON-COMBUSTIBLE USE APPROVED EXTENDER RINGS - METAL NOT APPROVED 4. BOXES MORE THAN 1/8" FROM EDGE - 314.21 5. MISSING CIRCUIT DIRECTORIES 6. WE HAVE OPEN NEUTRAL LIGHTING CIRCUITS NOT ON ARC FAULT PROTECTION PER ACTING BUILDING OFFICIAL 7. GROUNDED RECEPTACLES ON UNGROUNDED CIRCUIT |
|
| 08/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE ARC FAULT PROTECTION FOR ALL 120V OUTLETS IN SLEEPING AREAS - NEC 210.12, 210.18 2. PANEL DIRECTORY NOT CORRECT - NEC 408.4, NUMBER BREAKERS - MAKE DIRECTORIES LEGIBLE, NO SCRIBBLING, ETC 3. 4/0 AL FEEDER TO BE PROTECTED WITH MAX 200 AMP BREAKER - NEC 210.15 4. UNITS ARE OCCUPIED PRIOR TO APPROVAL 5. EXTERIOR LIGHTING NOT WORKING - PANEL TO BE UNLOCKED 6. PERSONAL BELONGINGS/FURNITURE NOT TO BE IN ROOMS 7. FIRE ALARM NOT COMPLETE MEETING WAS TO TAKE PLACE - BUT NO ONE SHOWED? |
|
| 08/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ALL RANGE ANTI-TIP DEVICES, REMOVE BONDING JUMPER AND INSTALL CORD CONNECTOR PROPERLY. 2. NEED BOX EXTENDERS FOR MICRO RECEPTACLES 3. EXTERIOR LIGHTING TO BE INSTALLED & WORKING 4. PANEL DIRECTORY NOT CORRECT 5. 2 NEUTRALS NOT ALLOWED UNDER SAME TERMINATION IN PANEL 6. PROVIDE ARC FAULT PROTECTION PER NEC 210.12 (2002) INSPECTION FOR UNIT #190 ONLY -- CHECK ALL UNITS #193, 192, 191, 297, 296 STILL NO ROUGH INSPECTION PLANS TO BE ACCURATE AND SHOW ANY SITE WORK WILL LOOK AT SERVICE AND DISTRIBUTION PANELS NEXT TIME. |