Permit: T07CM01812

Parcel: 115180050


Addresses:

1601 N ORACLE RD 01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/05/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUB-PANEL WALL IN WEIGHT ROOM
08/29/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK COVER BUILDING #1 ALL UNITS EXCEPT
#193, 192, 191, 297, 296

STILL NEED TO REVISE PLANS - UNITS BEING WIRED AS DWELLING UNITS.
07/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STILL NEED TO REVISE PLANS TO SHOW UNITS TO BE WIRED AS A DWELLING UNIT AND ALL APPLICABLE NEC REQUIREMENTS OF A DWELLING UNIT
2. UNIT #193 - NR
3. UNITS #192 & #191 NEED TO BE UNCOVERED FOR INSPECTION
4. PROVIDE A GROUND BAR FOR SUB-PANELS AND SEPARATE GROUNDS AND NEUTRALS.
5. USE 14GA WIRE TO FEED EXISTING 14GA CKTS
6. PROVIDE DEDICATED 20AMP BATH GFI
7. KITCHEN CKT NOT TO BE SHARED ON LIGHTING CKT

READ NEC 210
06/18/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/13/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) INSPECTION ONLY #192: NEED LETTER FROM ENGINEER CONCERNING USAGE OF EXISTING NON GROUNDED WIRING (14 GA)
2) WIRING NOT PER PLAN
3) NEED A/C POWERED SMOKE DETECTOR
4) ROMEX NOT TO BE STAPLED ON SIDE, INSTALL NAIL PLATES, MAKE UP PANELS, WIRING. TIGHTEN GROUND SCREWS
5) UNITS MEET NEC DEFINITION OF A DWELLING UNIT AND SHOULD BE WIRED AS SUCH ?