Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUB-PANEL WALL IN WEIGHT ROOM |
|
| 08/29/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK COVER BUILDING #1 ALL UNITS EXCEPT #193, 192, 191, 297, 296 STILL NEED TO REVISE PLANS - UNITS BEING WIRED AS DWELLING UNITS. |
|
| 07/13/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STILL NEED TO REVISE PLANS TO SHOW UNITS TO BE WIRED AS A DWELLING UNIT AND ALL APPLICABLE NEC REQUIREMENTS OF A DWELLING UNIT 2. UNIT #193 - NR 3. UNITS #192 & #191 NEED TO BE UNCOVERED FOR INSPECTION 4. PROVIDE A GROUND BAR FOR SUB-PANELS AND SEPARATE GROUNDS AND NEUTRALS. 5. USE 14GA WIRE TO FEED EXISTING 14GA CKTS 6. PROVIDE DEDICATED 20AMP BATH GFI 7. KITCHEN CKT NOT TO BE SHARED ON LIGHTING CKT READ NEC 210 |
|
| 06/18/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/13/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) INSPECTION ONLY #192: NEED LETTER FROM ENGINEER CONCERNING USAGE OF EXISTING NON GROUNDED WIRING (14 GA) 2) WIRING NOT PER PLAN 3) NEED A/C POWERED SMOKE DETECTOR 4) ROMEX NOT TO BE STAPLED ON SIDE, INSTALL NAIL PLATES, MAKE UP PANELS, WIRING. TIGHTEN GROUND SCREWS 5) UNITS MEET NEC DEFINITION OF A DWELLING UNIT AND SHOULD BE WIRED AS SUCH ? |