Permit: T07CM01792

Parcel: 10821328B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTRACTOR NOT ON SITE, LOCKED
06/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BREAKERS NEED TO GO TO WHAT THEY SAY THEY ARE GOING TO.
THEY ALSO MUST SAY THEY ARE FOR #300 CHECK EACH BREAKER FOR #300 AND MAKE SURE ALL IS CORRECT AND PROPERLY IDENTIFIED - A REFEE MAY BE CHARGED IF ALL NOT CORRECT NEXT INSPECTION
06/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PANEL DIRECTORY NOT CORRECT, LEGIBLE, NEAT NEC 408.4
2) INSTA HOT NOT IN
3) NEED TO PAY REFEE
4) OK TEMP C OF O
06/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTA-HOT TO BIG FOR 20 AMP CKT
2. PANEL DIRECTORY STILL NOT COMPLETE, OR CORRECT
3. PROVIDE PROPER GROUND PATH & GROUND J-BOX

WILL NEED TO PAY REINSPECTION FEE
IF NOT CORRECT NEXT TIME.

BRANDON 609-6960
06/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CKT TO INSTA-HOT UNDERSIZED - NEC 422.10
2. TIGHTEN ALL LOOSE RECEPTACLES - NEC 406.4
3. PANEL DIRECTORY NOT CORRECT - NEC 408.4
4. NEW CKTS PULLED? HAVE PANEL COVER & BRANCH CKT J BOX OPEN