Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01792
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONTRACTOR NOT ON SITE, LOCKED |
|
06/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BREAKERS NEED TO GO TO WHAT THEY SAY THEY ARE GOING TO. THEY ALSO MUST SAY THEY ARE FOR #300 CHECK EACH BREAKER FOR #300 AND MAKE SURE ALL IS CORRECT AND PROPERLY IDENTIFIED - A REFEE MAY BE CHARGED IF ALL NOT CORRECT NEXT INSPECTION |
|
06/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANEL DIRECTORY NOT CORRECT, LEGIBLE, NEAT NEC 408.4 2) INSTA HOT NOT IN 3) NEED TO PAY REFEE 4) OK TEMP C OF O |
|
06/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTA-HOT TO BIG FOR 20 AMP CKT 2. PANEL DIRECTORY STILL NOT COMPLETE, OR CORRECT 3. PROVIDE PROPER GROUND PATH & GROUND J-BOX WILL NEED TO PAY REINSPECTION FEE IF NOT CORRECT NEXT TIME. BRANDON 609-6960 |
|
06/11/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CKT TO INSTA-HOT UNDERSIZED - NEC 422.10 2. TIGHTEN ALL LOOSE RECEPTACLES - NEC 406.4 3. PANEL DIRECTORY NOT CORRECT - NEC 408.4 4. NEW CKTS PULLED? HAVE PANEL COVER & BRANCH CKT J BOX OPEN |