Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM01792
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/24/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TIE WIRES CONNECTED TO CEILING LIGHTS TO BE CONNECTED INDEPENDENT TO BUILDING STRUCTURE. 2. CANNOT USE TIE WIRES FOR SUPPORT OF CEILING AS SUPPORT FOR MC CABLE. INDEPENDENT SUPPORT REQUIRED. 3. SEAL OPEN 1/2" KNOCK OUT IN VAV CONTROL BOX 4. SEAL OPEN KNOCKOUTS IN JUNCTION BOX 5. REMOVE OLD TELEPHONE WIRES |