Permit: T07CM01791

Parcel: 136218630

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/11/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) REPLACE BOX AT OUTSIDE LIGHT
2) OK WALLS
06/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE SHEETROCK & INSULATION FOR INSPECTION
2. ADD RECEPTACLE TO BACK OF HOUSE FOR OUTDOOR USE
3. SMOKE DETECTORS NEED TO BE INTERCONNECTED WITH EXISTING SMOKE DETECTORS.
4. STAPLE SECURE ROMEX PER NEC 334 WITHIN 8" OF SINGLE GANG PLASTIC BOXES & EVERY 54" BETWEEN
5. MAKE UP ALL CONNECTIONS/SPLICES IN BOXES
INSTALL BARREL CRIMP OR WIRE NUT ON GROUND SPLICES
6. INSTALL BOX FOR OUTDOOR LIGHT