Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01777
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/06/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SECURE POWER POLE TO CEILING GRID 2. FURNITURE NOT COMPLETELY WIRED 3. MISSING GROUND & NEUTRAL ON OUTLETS IN WORK STATIONS. 4. RECALL WHEN ALL WORK COMPLETE 5. WORK STATIONS IN PHASE 2 COMPLETE |
|
06/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RECALL FOR POWER POLES & OFFICE FURNITURE OK FOR TEMP C OF O |
|
06/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY & EXIT LIGHTS ON EAST SIDE OF SPACE NEED TO BE ON EMERGENCY CIRCUIT. TO AVOID REFEE HAVE CORRECTED BEFORE NEXT INSPECTION |
|
06/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EMERGENCY LIGHTING NOT PER PLAN |
|
06/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3 RECEPTACLES HAVE NO POWER 2. NEED TO CHECK EMERGENCY LIGHTING 3. POWER POLES NOT INSTALLED AT THIS TIME |
|
06/12/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK OFFICES PHASE 1 EAST 2. NEED TO INSPECT POWER POLES WHEN INSTALLED 3. WILL CHECK OUT EMERGENCY LIGHTING AT END OF JOB |