Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01774
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
12/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING CONDUCTORS TO BE CONNECTED TO LIGHT POLES 2. STRAP LIQUID TIGHT WITHIN 12" OF CONNECTION POINTS 3. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION 4. HAVE PANEL UNLOCKED 5. HAVE PLANS ON SITE 6. HAVE GATE OPERATION EQUIPMENT OPEN 7. CANNOT USE PLUMBING FITTINGS FOR CONNECTION OF ELECTRIC PVC |
|
11/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ONE LINE DIAGRAM TO BE REVISED AND RESUBMITTED TO SHOW UNDERGROUND SERVICE |
|
10/17/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |