Permit: T07CM01767

Parcel: 11706162B


Addresses:

75 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01767

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SIZE SERVICE CONDUCTORS FOR 400 AMP SERVICE PER
NEC 310.16 & 230.42
2. INSTALL GROUNDING ELECTRODES AT EACH STRUCTURE PER NEC 250.32
3. INSTALL GROUNDING CONDUCTOR WITH EACH FEEDER TO SEPARATE STRUCTURES PER NEC 250.32
4. INSTALL PLASTIC BUSHING ON CONDUIT ENTRIES WITH #4 OR LARGER CONDUCTORS PER NEC 300.4 & 352.46
5. CANNOT FEED ONE PANEL THROUGH ANOTHER PER
NEC 312.8 - INSTALL SEPARATE CONDUITS TO EACH PANEL.
6. INSTALL PANEL DIRECTORY PER NEC 408.4
06/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The inspector was unable to locate the job.| 945*
COULD NOT LOCATE ADDRESS
06/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*