Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01767
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SIZE SERVICE CONDUCTORS FOR 400 AMP SERVICE PER NEC 310.16 & 230.42 2. INSTALL GROUNDING ELECTRODES AT EACH STRUCTURE PER NEC 250.32 3. INSTALL GROUNDING CONDUCTOR WITH EACH FEEDER TO SEPARATE STRUCTURES PER NEC 250.32 4. INSTALL PLASTIC BUSHING ON CONDUIT ENTRIES WITH #4 OR LARGER CONDUCTORS PER NEC 300.4 & 352.46 5. CANNOT FEED ONE PANEL THROUGH ANOTHER PER NEC 312.8 - INSTALL SEPARATE CONDUITS TO EACH PANEL. 6. INSTALL PANEL DIRECTORY PER NEC 408.4 |
|
06/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The inspector was unable to locate the job.| 945* COULD NOT LOCATE ADDRESS |
|
06/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |