Permit: T07CM01765

Parcel: 13323111Q


Addresses:

7727 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01765

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
FINISH PREVIOUS INSPECTIONS
UNUSED OPENING
VDV CABLING
11/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FILL UNUSED OPENING IN JUNCTION BOX - NOT ENTRY FITTING
2. BUZZER COMPONENTS NOT INSTALLED AS PER PLANS
REVISE PLANS OR INSTALL AS PER PLANS --NOTES 5 & 8
08/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO CONTRACTOR ON SITE, CALLED AND LEFT MESSAGE THAT I WAS ON THE WAY
2) RECALL WHEN READY
08/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
08/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. OPEN CEILING & HAVE LADDER ON SITE FOR ABOVE CEILING INSPECTION IN GROOMING AREA
2. ALL OTHER INSPECTION ITEMS CORRECTED
08/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE EMT FOR SUPPORT OF TELEPHONE/DATA LINES
2. TIE WIRES FOR FIXTURES TO BE ROUTED THROUGH HOLES IN CLIPS
3. INSTALL BOX EXTENSION ON RECEPTACLE BOXES MORE THAN 1/4" BACK FROM FINISHED SERVICE
4. TIE WIRE USED TO SUPPORT EMT/BOXES/WIRING TO BE SECURED AT BOTH ENDS
5. ROOFTOP SERVICE RECEPTACLE HAS NO POWER
6. POWER WIRING RUN TO ROOFTOP UNIT TO BE INSTALLED IN CONDUIT INSIDE UNIT UP TO DISCONNECT.