Permit: T07CM01765

Parcel: 13323111Q


Addresses:

7727 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/08/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/20/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/14/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/02/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/31/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. EXISTING VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6
2. BOXES OVERFILLED
3. SUPPORT CONDUIT & BOXES AS PER 300.11
4. EACH FIXTURE TO HAVE 2 SUPPORT WIRES
5. INSTALL FIXTURE FITTINGS INTO FIXTURES - WHIPS