Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01752
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS |
|
11/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | 1. EMERGENCY LIGHTING TO BE PER PLAN/FED FROM NORMAL LIGHTING CKT FOR THAT AREA - NEC 700.12F 2. BOND 480 RACEWAYS WHERE CONCENTRICS OR ECENTRICS ARE ENCOUNTERED - NEC 250.97 3. SPLIT BOLTS IN GUTTER TO BE USED FOR # OF CONDUCTORS LISTED FOR NEC 110.3B 4. NEED DISCONNECTING MEANS FOR HOT WATER HEATER NEC 422.31B 5. ADD BOX EXTENDERS AS NEEDED - NEC 314.20 6. RECEPTACLES NOT TO BE LOOSE OR SET BACK FROM FACE NEC 406.4 |