Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01752

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
11/07/2007 ELECTRIC - FINAL Not ready for Inspection 1. EMERGENCY LIGHTING TO BE PER PLAN/FED FROM NORMAL LIGHTING CKT FOR THAT AREA - NEC 700.12F
2. BOND 480 RACEWAYS WHERE CONCENTRICS OR ECENTRICS ARE ENCOUNTERED - NEC 250.97
3. SPLIT BOLTS IN GUTTER TO BE USED FOR # OF CONDUCTORS LISTED FOR NEC 110.3B
4. NEED DISCONNECTING MEANS FOR HOT WATER HEATER
NEC 422.31B
5. ADD BOX EXTENDERS AS NEEDED - NEC 314.20
6. RECEPTACLES NOT TO BE LOOSE OR SET BACK FROM FACE NEC 406.4