Inspection Status: Not Applicable

Inspection History: ELECTRIC - PROGRESS

Permit Number - T07CM01752

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Not Applicable

Date Description Inspector Results Comments
11/15/2007 ELECTRIC - PROGRESS Not Applicable IVRS - Inspection :*
10/24/2007 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR SERVICE ONLY
1. IDENTIFY SPACE # AT METER AND DISCONNECT,
NOT OUTER DOOR
2. PNL TO HAVE PROTECTIVE BUSHING FOR FEEDERS INTO GEAR
3. INSTALL MISSING FUSE, PLANS CALL FOR LPS TYPE FUSES
4. INSTALL FUSES IN TRANSFORMER DISCONNECT
5. CONDUCTORS PANEL P TO J-BOX TO BE DERATED PER
NEC 310.15 B 2A
6. STILL NEED TO SEE EXISTING SERVICE BOND TO STEEL
(FOR TRANSFORMER G.E.C)
7. STRAP TRANSFORMER LOAD SIDE FLEX