Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | ELECTRIC - PROGRESS | Not Applicable | IVRS - Inspection :* | |
| 10/24/2007 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SERVICE ONLY 1. IDENTIFY SPACE # AT METER AND DISCONNECT, NOT OUTER DOOR 2. PNL TO HAVE PROTECTIVE BUSHING FOR FEEDERS INTO GEAR 3. INSTALL MISSING FUSE, PLANS CALL FOR LPS TYPE FUSES 4. INSTALL FUSES IN TRANSFORMER DISCONNECT 5. CONDUCTORS PANEL P TO J-BOX TO BE DERATED PER NEC 310.15 B 2A 6. STILL NEED TO SEE EXISTING SERVICE BOND TO STEEL (FOR TRANSFORMER G.E.C) 7. STRAP TRANSFORMER LOAD SIDE FLEX |