Permit: T07CM01748

Parcel: 107144320


Addresses:

2573 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/26/2007 ELECTRIC - FINAL Approved MAXIMUM OVERCURRENT DEVICE FOR INSTA-HOT'S TO BE PER NEC 422.11 E3
10/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTA-HOT CKT'S TO BE HARD-WIRED AND HAVE
MINIMUM 25 AMP. RATED CKT, SEE NEC 422.10 E3
GFI NOT TO BE USED AS CONNECTION - NEC 400.8

THEY WILL STILL NEED A DISCONNECTING MEANS -
NEC 422.31B

2. PANEL DIRECTORY TO BE CORRECT - NEC 408.4