Permit: T07CM01748

Parcel: 107144320


Addresses:

2573 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/26/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WATER HEATER CKT UNDERSIZED -- NEC 110.3, 422
2. GROUND ALL METAL BOXES
3. CALCULATIONS FOR SERVICE NOT CORRECT - THESE CALCS TO SHOW ACTUAL LOADS

OK TO DRYWALL
08/09/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE OPEN/ILLEGAL WIRING IN WALL @ ENTRY FOR UNIT NEXT DOOR
2. HAVE OVERFILLED BOXES - NEC 314.16
3. HAVE OVERFILLED WIRE NUTS - NEC 110.3 B
4. GROUND ALL J-BOXES - NEC 250.148
5. PROVIDE NAIL PLATES - NEC 330.17
6. WIRING NOT PER PLAN
7. FRAME ATTIC ACCESS