Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. WATER HEATER CKT UNDERSIZED -- NEC 110.3, 422 2. GROUND ALL METAL BOXES 3. CALCULATIONS FOR SERVICE NOT CORRECT - THESE CALCS TO SHOW ACTUAL LOADS OK TO DRYWALL |
|
| 08/09/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OPEN/ILLEGAL WIRING IN WALL @ ENTRY FOR UNIT NEXT DOOR 2. HAVE OVERFILLED BOXES - NEC 314.16 3. HAVE OVERFILLED WIRE NUTS - NEC 110.3 B 4. GROUND ALL J-BOXES - NEC 250.148 5. PROVIDE NAIL PLATES - NEC 330.17 6. WIRING NOT PER PLAN 7. FRAME ATTIC ACCESS |