Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM01739
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2007 | FRAMING | Approved | IVRS - Inspection :* | |
08/23/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* ITEM #2 NOT MET |
|
08/01/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCK ALL MECHANICAL DUCT VENTS 3 SIDES 2) PROTECTION PLATES NEEDING ON PLUMBING AND VENT PIPING AT VARIOUS LOCATION-THROUGHOUT. ANYTHING LESS THAN 1.25 INCHES NEEDS A PROTECTION PLATE 3) NEED STUD SHOES ON OVERNOTCHED 2 X 6 STUDS AT LAUNDRY ROOM 4) SEPERATE WIRE BUNDLES AT HOME RUN COMING OUT OF SERVICE PANEL 5) PEX WATER LINE AT LIVING ROOM NEEDS TO BE SUPPORTED ABOVE CEILING LINE 6) NEGATIVE PITCH ON TRAP ARM AT BATH OF #2 BEDROOM 7) VENT PIPE AT BATH BETWEEN BEDROOM #3 & #4 NEEDS CLEARANCE AT WALL 8) WATER LINES AT KITCHEN NEEDS TO BE MOVED 12" AWAY FROM CAN LIGHTS. MECHANICAL FLEX DUCT NEEDS TO BE STAPLED AND HUNG EVERY 5' FROM TRUSS 9) MISSING CLEANOUTS PER PLAN 10) NO DWV TEST 11) STOPPED INSPECTION |