Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/30/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OUTLET REQUIRED PER CODE @ PENISULA 2. SECURE 90 VENT THROUGH ROUGH UPSTAIRS NAIL PROTECT VENT @ BASE AND LAUNDRY VENT & DRAIN 3. TERMINATE ROMEX IN APPROVED BOX UPSTAIRS CLOSET FIXTURE 4. GROUT TUB SHOE 5. SECURE HOME RUNS & COMPLETE ALL RUNS TO PANEL 6. PLEASE CLEAR PROJECT OF DEBRIS PRIOR TO NEXT INSPECTION |
|
| 07/27/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/21/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSPECTED DWV TEST OK |
|
| 08/14/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOT COMPLETED FOR INSPECTION |
|
| 03/12/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLUMBING YARD WATER NOT COMPLETE-NEEDS BLUE TRACER WIRE FROM METER TO STUB UP RISER 2) MISSING ANTI-SIPHON ON HOSE BIBS 3) NO DWV TEST AVAILABLE 4) AAV NOT PLUMB PROPERLY 5) MISSING TRAP AT BATH/TUB |