Permit: T07CM01731

Parcel: 11703145B


Addresses:

818 N 10TH AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/12/2010 FRAMING Approved IVRS - Inspection :*
08/05/2009 FRAMING Partial Approval IVRS - Inspection :*
1) BLOCK BOOT 3 SIDES KITCHEN
07/27/2009 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST ADDRESS VISIBLE FROM STREET
2) NAIL PROTECT PLUMBING THROUGHOUT UPSTAIRS
3) TERMINATE ALL ROMEX IN APPROVED BOXES
4) INSTALL TUB
5) TERMINATE ROMEX INSULATION IN BOXES
6) SECURE 4 GANG BOXES BOTHY SIDES
7) STOPPED INSPECTION
08/27/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/17/2007 FRAMING Partial Approval IVRS - Inspection :*
1) OK TO CONTINUE ON INSPECTED WALLS ONLY
2) INSPECTED ALL 3 LIVING ROOM WALLS UP TO 4 BALES AND KITCHEN AND DINING AREA ALSO EAST WALL
3) KEEP IN MIND #4 REBAR NEEDS TO BE CENTERED ON BALES
4) YOUR FILLABLE UNTIED FLAKES NEED TO BE COMPACTED A LITTLE TIGHTER IN SOME PLACES
08/16/2007 FRAMING Not ready for Inspection IVRS - Inspection :*