Permit: T07CM01726

Parcel: 137080490


Addresses:

334 W HOLLADAY DR

Inspection Status: Denied

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
03/10/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED MORE INFORMATION FOR GLU-LAM THEY HAVE EXTEDNED IT PAST 2 X 4 WALL AND CONNECTED TO DBL 2 X 10 WITH A LUSD LAYER. NEED SUPPORT POST ?
2) NEED WIND BRACE AT CORNER OF BLDG OR SHEATHING
3) INSPECTED ALL CLIPS ON EXT WALLS OK
4) NEED 2 X 4 STUD AT TOP PLATE TO BOTTOM PLATE AT WEST EXT WALL (ONE PLACE)
5) OK TO DRY IN ROOF