Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 07/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL ALL STRANDS INTO BOND BUSHING LUGS 2) FEED LINE SIDE OF PANEL 'A' DISCONNECT AND CORRECTLY IDENTIFY 3) IDENTIFY GROUNDED CONDUCTOR WITH WHITE TAPE |
|
| 06/25/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. A NEUTRAL KIT FOR MAIN DISCONNECT 2. SEAT CONDUITS IN FITTING AND TIGHTEN 3. FINISH LINE SIDE OF PANEL "A" 4. NEED REJECTION PINS AT MAIN |
|
| 07/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK PANEL CORRECTIONS |
|
| 07/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* SEPARATE GROUNDS AND NEUTRALS AT SUB-PANEL (250.24) |
|
| 07/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |