Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/24/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CONTR. TO RECALL INSP. CONSULT WITH INSPECTOR OF AREA |
|
| 07/10/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/24/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/04/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/02/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 03/19/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. JUNCTION BOX TO BE ACCESSIBLE 2. PROTECT M/C CABLE AT TOP PLATE 3. BOXES OVERFILLED 4. EM & EXIT LIGHTING TO BE ON CIRCUIT FOR AREA SERVED 700.12 5. STRAP MC CABLES WITHIN 12" OF BOXES & CANS 6. USE APPROVED STRAPS FOR M/C CABLES 7. PLEASE VERIFY PANEL CIRCUITS & LOADS - DOES NOT MATCH INSTALLED ALSO SERVICE 8. SECURE CABLES TO PANEL ENCLOSURE 9. PLEASE ADD 02035 TO PERMIT TO INSPECT WALLS 10. REVISE PLANS TO REFLECT LIGHTING INSTALLED |
|
| 03/18/2008 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled |