Permit: T07CM01716

Parcel: 11202033P


Addresses:

2000 E ROGER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FAX ME THAT SPEC SHEET WE TALKED ABOUT
08/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED CUTLER HAMMER BR TYPE BREAKER
2. STRAM EMT @ PANEL & J-BOX
3. PROVIDE SHEET FOR REMOTE TRANSFORMER INSTALLATION
08/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY FOR N.W GATE
1. EXTEND 120V RACEWAYS INTO GATE MOTOR J-BOXES
NEC 300.18
2. GROUND J-BOXES WITH EQUIPMENT GROUND - NEC 250.148
3. TIGHTEN ALL FITTINGS -- NEC 358.42
4. HAVE WATER IN J-BOX?
5. USE STRUT STRAPS FOR EMT ON ROOF
6. PHONE LINE ON ROOF TO BE RAN NEAT AND IN A WORKMANLIKE MANNER - NOT TRIPPING HAZARD - NEC 800
7. SECURE EMT TO ROOF
8. OPEN WIRING NOT ALLOWED DOWN HALL
9. IDENTIFY CKT AT PANEL DIRECTORY
10. GATE TO BE FULLY OPERATIONAL FOR FINAL