Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01716
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FAX ME THAT SPEC SHEET WE TALKED ABOUT |
|
08/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED CUTLER HAMMER BR TYPE BREAKER 2. STRAM EMT @ PANEL & J-BOX 3. PROVIDE SHEET FOR REMOTE TRANSFORMER INSTALLATION |
|
08/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY FOR N.W GATE 1. EXTEND 120V RACEWAYS INTO GATE MOTOR J-BOXES NEC 300.18 2. GROUND J-BOXES WITH EQUIPMENT GROUND - NEC 250.148 3. TIGHTEN ALL FITTINGS -- NEC 358.42 4. HAVE WATER IN J-BOX? 5. USE STRUT STRAPS FOR EMT ON ROOF 6. PHONE LINE ON ROOF TO BE RAN NEAT AND IN A WORKMANLIKE MANNER - NOT TRIPPING HAZARD - NEC 800 7. SECURE EMT TO ROOF 8. OPEN WIRING NOT ALLOWED DOWN HALL 9. IDENTIFY CKT AT PANEL DIRECTORY 10. GATE TO BE FULLY OPERATIONAL FOR FINAL |