Permit: T07CM01716

Parcel: 11202033P


Addresses:

2000 E ROGER RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T07CM01716

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
OK TO COVER TRENCH BETWEEN I & H, 24" DEEP
05/31/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. UNDERGROUND AT BLDG I EASTSIDE, CONDUITS UNDER DRIVEWAY MUST BE 24" BELOW DRIVEWAY GRADE, IN ISLAND IT'S TO BE 18" DEEP.
2. MAIN GATE AREA OK TO COVER
3. FAR EAST UNDERGROUND OK TO COVER
05/25/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. AREA BY LEASING OFFICE -- (2) 3/4" PVC, 30" DEEP OK
2. AREA BY BUILDING 1 WEST -- NO CONDUIT IN YET
3. AREA EAST SIDE OF BUILDING 1 NOT DUG YET

1ST TRENCH WITH PIPE IN IT -- OK TO COVER.