Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM01715
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/02/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999$ 1. MOUNT WATER HEATER DISCONNECT BELOW CEILING SINCE WATER HEATER WILL BE BELOW CEILING. ALSO, WRAP EQUIPMENT GROUND AROUND GROUND SCREW IN DISCONNECT, WIRING TO WATER HEATER NOT COMPLETE NEC 422.31 2. ALL LOW VOLTAGE WIRING TO BE SUPPORTED FROM STRUCTURE, NOT LAYING ON GRID OR OTHER EQUIPMENT 3. PROVIDE A MINIMUM 6' LADDER INSPECTION |
|
| 06/27/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK LIGHTING IN SOFFIT AREAS |