Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01714
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR NOT ON SITE. IF ADVANCE CALL IS NEEDED, PLEASE LEAVE # TO CALL WITH MESSAGE, ALSO, NEED THE REVISED PLANS ON SITE. |
|
06/15/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
06/15/2007 | ELECTRIC - FINAL | Partial Approval | ROOF: 1-SUPPORT SEAL TITE UP OFF OF ROOF AND AS PER CODE 2-TIGHTEN LOOSE FITTINGS 3-CORRECT 2/WIRE EXHAUST FAN 4-WAITING ON PLAN REVISION OK TCO SUBJECT TO DETERMINATION OF STEVE LONG |
|
06/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ROOF: FINISH ELECTRICAL WORK 2) WAITING ON PLAN REVISIONS |
|
06/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED MAIN IN PANEL CS5A OR REVISE PLANS 2) CLEAN EXCESS DIRT FROM PANELS 3) LABEL PANEL SCHEDULES PER 408.4 NO ABREVIATIONS AND IDENTIFY DIFFERENCES 4) TAPE IS NOT AN APPROVED MEANS FOR BLANKING/SEALING 5) ONLY ONE CONDUCTOR PER TERMINAL LUG, ALSO INSTALL ALL STRANDS UNDER LUG 6) BOND CONTACTOR ENCLOSURE AND TRANSFORMER ENCLOSURE AND INSTALL MAIN BONDING JUMPER 7) FINISH FIRE ALARM BOXES AND WIRING 8) FINISH WIRING A/C SERVER ROOM 9) CORRECTLY SUPPORT M/C CABLES ABOVE "C54" 10) COLOR FOR CONDUCTORS TO BE BROWN, ORANGE, YELLOW 277/480V AND BLACK, RED AND BLUE 120/208 11) RECONNECT GROUNDING ELECTRODE CONDUCTOR FOR TRANSFORMER 210.5 (C) AMENDMENTS |