Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/12/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/12/2007 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 06/12/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILINGS |
|
| 06/11/2007 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 06/11/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. BLANK OPEN ENDS OF SPARE CONDUITS INTO COMPUTER ROOM PANELS 2. OPEN JUNCTION BOXES IN CEILING OF COMPUTER ROOM 3. SUPPORT METAL FLEX IN COMPUTER ROOM CEILING GET IT UP OFF OF GRID 4. OK TO CLOSE CEILING IN OPEN AREA |