Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BLANK OPEN BREAKER POSITIONS 2. FINISH PANEL DIRECTORIES 3. FINISH ELECTRIC IN BAND BOX 4. NEED DISCONNECTING MEANS FOR INSTANT HOTS - NEC 422.31 5. EM LIGHTS CONTROL RM. NOT WORKING 6. SOME OUTDOOR LIGHTING FIXTURES NOT WORKING 7. SOME OUTDOOR EM. LIGHTS NOT WORKING 8. DISCONNECTING MEANS FOR AC.4 TO BE WITHIN SIGHT OF UNIT NEC 440.14 |