Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BLANK OPEN BREAKER POSITIONS
2. FINISH PANEL DIRECTORIES
3. FINISH ELECTRIC IN BAND BOX
4. NEED DISCONNECTING MEANS FOR INSTANT HOTS -
NEC 422.31
5. EM LIGHTS CONTROL RM. NOT WORKING
6. SOME OUTDOOR LIGHTING FIXTURES NOT WORKING
7. SOME OUTDOOR EM. LIGHTS NOT WORKING
8. DISCONNECTING MEANS FOR AC.4 TO BE WITHIN SIGHT OF UNIT NEC 440.14