Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/02/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/28/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. OPEN BOX @ 102, EAST HALLWAY
2. MISSING KNOCKOUT JUNCTION BOX EAST HALLWAY
CHECK ALL BOXES
3. OK CEILINGS MAIN ENTRY
4. INSTALL TIE WIRE ON FIXTURE WEST HALLWAY, CHECK ALL FIXTURES
5. REMOVE TEMP LIGHTS/CORDS ETC.
6. HAVE ELECTRICAL CONTRACTOR GO THROUGH ALL CEILINGS AND MAKE CORRECTIONS AS NEEDED
08/27/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECEIVED GFI TEST REPORT
08/22/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY FRED
08/13/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK U.G @ MAIN ENTRY
- FLOOR BOXES
- LIGHTING CIRCUITS
08/05/2008 ELECTRIC - INTERMEDIATE Partial Approval 1. INSTALL TIE WIRES ON EXITS THEN OK CEILING
2. OK WALL @ ENTRY
07/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ORCHESTRA SHELL RM #123
07/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSPECTION ITEMS FROM 7/2/08 COMPLETED EXCEPT ITEM #4
NEED TO HAVE GFI PERFORMANCE TEST DONE PER NEC 215.10 AND 230.95
07/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS BOOM BOX 2 RM 202
07/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PANEL XFMR INSPECTION
1. SIZE BONDING JUMPERS & SYSTEM BONDING JUMPER PROPERLY. XFMR & PANELS
2. MISSING 2ND NEUTRAL FROM 75 KVA XFMR
3. CONNECT EG TO XFMR
4. NEED TO HAVE GFI PERFORMANCE TEST ON BREAKER
5. MAKE ALL CORRECTIONS AS DISCUSSED
07/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS. 123, 124, 125, 115
06/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & SOFFITS UPPER SEATING AREA
06/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS CONTROL RM & CONTROL RM STAIRWAY
05/30/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
05/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS RESTROOM BUILDINGS
2. OK CEILINGS RESTROOM BUILDING
04/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
COURTESY INSPECTION OF CEILING ABOVE SEATING AREA
NEED MORE STRAPPING OF EMT
04/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS 115, 116, 117, 118, 119
02/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS BACKSTAGE AREA