Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01702

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ADDRESS LABEL TO BE PERMANENT METAL
2. SECURE GROUNDING ELECTRODE CONDUCTOR TO PEDESTAL
3. DRIVE GROUNDS FLUSH WITH GRADE
4. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED CONDUCTOR TERMINAL
5. INSTALL ALL STRANDS UNDER LUGS
6. LABEL BREAKERS
7. TIGHTEN CORD STRAIN RELIEF CONNECTOR
8. CONNECT GROUNDING ELECTRODE CONDUCTOR FROM TRAILER TO GROUNDING ELECTRODE SYSTEM.
9. PLEASE VERIFY CORD USAGE FOR WET LOCATION 400.4