Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01697
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RE-IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS 2. INSTALL ALL SCREWS FOR SUPPORT OF RECEPTACLES IN INDUSTRIAL COVERS 3. DISPOSAL CORD TO BE 18"-36" DISHWASHER TO BE 48" MAX 4. INSTALL EXTENSION ON RECEPTACLE UNDER SINK AND FOR MICROWAVE 5. INSTALL ANTI-TIP ON RANGES 6. ALL BEDROOM OUTLETS TO BE ARC-FAULT PROTECTED THIS INCLUDES RECEPTACLES, LIGHTS, FANS, SMOKES 7. ONE NEUTRAL PER TERMINAL IN PANEL 8. CHECK ALL THREE UNITS |
|
12/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SERVICE INSPECTION 1. INSTALL BONDING JUMPER ON RISER TO SERVICE PANEL 2. JACKET ON ROMEX TO EXTEND INTO SERVICE PANEL MIN. 1/4" 3. SEAL OPENINGS IN BACK OF PANEL WHERE WIRES ENTER WITH NON-COMBUSTIBLE SEALANT 4. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR. |