Permit: T07CM01697

Parcel: 136048220


Addresses:

2501 S PANTANO PW


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01697

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RE-IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS
2. INSTALL ALL SCREWS FOR SUPPORT OF RECEPTACLES IN INDUSTRIAL COVERS
3. DISPOSAL CORD TO BE 18"-36" DISHWASHER TO BE 48" MAX
4. INSTALL EXTENSION ON RECEPTACLE UNDER SINK AND FOR MICROWAVE
5. INSTALL ANTI-TIP ON RANGES
6. ALL BEDROOM OUTLETS TO BE ARC-FAULT PROTECTED THIS INCLUDES RECEPTACLES, LIGHTS, FANS, SMOKES
7. ONE NEUTRAL PER TERMINAL IN PANEL
8. CHECK ALL THREE UNITS
12/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SERVICE INSPECTION
1. INSTALL BONDING JUMPER ON RISER TO SERVICE PANEL
2. JACKET ON ROMEX TO EXTEND INTO SERVICE PANEL
MIN. 1/4"
3. SEAL OPENINGS IN BACK OF PANEL WHERE WIRES ENTER WITH NON-COMBUSTIBLE SEALANT
4. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR.