Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01667
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO COMPLETE GROUNDING OF DISCONNECTS NEC 230.72 TO BE DONE WITH SERVICE UPGRADE AS DISCUSSED WITH HY KAPLAN THE ENGINEER. PLANS TO BE REVISED AND APPROVED. SEE NOTES FROM 9/19/07 |
|
| 09/19/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ALL PREVIOUS INSPECTION ITEMS TO BE COMPLETED 2) SERVICE CLEARANCE IS BASED ON REGISTER TO PLANS SHOWING RELOCATION OF SERVICE DISCONNECTS TO BE GROUNDED PER NEC 230.72. BOTH SETS OF PLANS TO BE REVISED FOR FUTURE WORK AND PRESENT WORK. THIS ACTIVITY WILL NOT BE FINALED UNTIL FUTURE WORK IS COMPLETED. ENGINEER WILL SUBMIT REVISIONS FOR APPROVAL 3) LABEL ALL SERVICE DISCONNECTS. SERVICE DISCONNECT 1 OF 4, 2 OF 4 ETC... |
|
| 09/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL MISSING LB COVER 2. INSTALL K.O SEAL AT AC UNIT DISCONNECT 3. NEED TO HAVE REVISED SET OF DRAWINGS SHOWING INSTALLATION AS IT WAS DONE. PLANS NEED TO BE APPROVED. 4. SERVICE DISCONNECTS NEED TO BE GROUPED - NEC 230.72 5. INSTALL MAIN BONDING JUMPER AT SERVICE DISCONNECT NEC 250.24 & NEC 250.28 6. NEED TO CLEAN UP GROUNDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS NEC 250.6 7. INSTALL GROUNDED CONDUCTOR (NEUTRAL) TO SERVICE DISCONNECT - NEC 250.24 8. HAVE ENGINEER VERIFY SPLICES/TAPS IN 4" X 4" WIRE WAY DO NOT EXCEED 75% OF THE AREA - NEC 376.56 9. NEED PROPER WORKING CLEARANCE IN FRONT OF DISCONNECT - NEC 110.26 |