Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM01666
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/24/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
02/23/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. WASTE VENT TOO CLOSE TO OUTSIDE AIR INLET 2. PROVIDE PROPER GROUND WIRE @ RTU DISCONNECT 3. PROVIDE PROPER AIR GAP AT CONDENSATE DRAIN 4. COMPLETE INSTALLATION OF ROASTER 5. E.F. NOT WORKING 6. ALL NOTES DATED 10/7/08 HAVE BEEN CORRECTED |
|
10/07/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE OUTSIDE AIR HOOD 2. PROVIDE AIR BALANCE REPORT (O.S.A) 3. CONDENSATE CANNOT TERMINATE AT A WASTE VENT 4. SUPPORT CONDUIT OFF OF ROOF 5. PROVIDE UNIT DATA ON DATA PLATE (HEAT STRIP) 6. PROVIDE SCREEN ON T-TOPS 7. PAINT ALL PVC EXPOSED TO WEATHER |