Permit: T07CM01666

Parcel: 115150510


Addresses:

501 W GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM01666

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/24/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/23/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. WASTE VENT TOO CLOSE TO OUTSIDE AIR INLET
2. PROVIDE PROPER GROUND WIRE @ RTU DISCONNECT
3. PROVIDE PROPER AIR GAP AT CONDENSATE DRAIN
4. COMPLETE INSTALLATION OF ROASTER
5. E.F. NOT WORKING
6. ALL NOTES DATED 10/7/08 HAVE BEEN CORRECTED
10/07/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE OUTSIDE AIR HOOD
2. PROVIDE AIR BALANCE REPORT (O.S.A)
3. CONDENSATE CANNOT TERMINATE AT A WASTE VENT
4. SUPPORT CONDUIT OFF OF ROOF
5. PROVIDE UNIT DATA ON DATA PLATE (HEAT STRIP)
6. PROVIDE SCREEN ON T-TOPS
7. PAINT ALL PVC EXPOSED TO WEATHER