Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01666
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK #4 TO REBAR IN FOOTING |
|
08/13/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS AND HARD LIDS |
|
08/06/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROTECT M/C CABLES AT WOOD STUDS 2) BOX OVERFILLED 3) SUPPORT VDV CABELING IN WALLS AND ABOVE HARD LIDS 725.24 AND 800.24 4) GUTTER TO MEET 366.22 & 23 5) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO BOTTOM OF FOOT 2"-3" 6) FILL UNUSED OPENING IN METER SOCKET 7) INSTALL SERVICE DISCONNECT MAIN BONDING JUMPER |