Permit: T07CM01665

Parcel: 13409018C


Addresses:

8640 E BROADWAY BL


Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T07CM01665

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
06/21/2007 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
TOP OUT OF MASONRY COLUMNS (8 EACH)
06/18/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
OK TO PROCEED
1. EAST, WEST & SOUTH CMU WALLS TOP OUT @ 5 FOOT
2. CMU PIERS (8) OK TO SECOND LIFT @ 56 INCHES
VIEW SPECIAL INSPECTORS REPORT & ENGINEERS STAMPED APPROVAL.
06/14/2007 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MUST HAVE TERRACON'S SPECIAL INSPECTION REPORT-APPROVED ON SITE
06/13/2007 REINFORCED MASONRY PRE-GROUT Denied 1. PLANS AND PERMITS MUST BE ON SITE AT ALL TIMES.
2. PREVIOUS INSPECTION REPORTS---INCLUDING SPECIAL INSPECTION REPORTS MUST BE ON SITE AT ALL TIMES.
3. COLLAR TIES (RINGS) IN COLUMNS DO NOT MATCH SPECIFICATIONS NOR ACI 318/340 REQUIREMENTS.
4. EXCESSIVE MORTAR FINS IN BLOCK.
5. GROUT CELLS BLOCKED WITH PAPER.
6. PREGROUT WILL NOT BE APPROVED WITHOUT SPECIAL INSPECTION REPORT ON SITE SHOWING THAT SPECIAL INSPECTOR HAS DETERMINED THAT STEEL IS IN CONFORMANCE WITH PLANS.
06/12/2007 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
05/30/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STEM WALL ONLY