Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T07CM01665
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2007 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* TOP OUT OF MASONRY COLUMNS (8 EACH) |
|
06/18/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* OK TO PROCEED 1. EAST, WEST & SOUTH CMU WALLS TOP OUT @ 5 FOOT 2. CMU PIERS (8) OK TO SECOND LIFT @ 56 INCHES VIEW SPECIAL INSPECTORS REPORT & ENGINEERS STAMPED APPROVAL. |
|
06/14/2007 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST HAVE TERRACON'S SPECIAL INSPECTION REPORT-APPROVED ON SITE |
|
06/13/2007 | REINFORCED MASONRY PRE-GROUT | Denied | 1. PLANS AND PERMITS MUST BE ON SITE AT ALL TIMES. 2. PREVIOUS INSPECTION REPORTS---INCLUDING SPECIAL INSPECTION REPORTS MUST BE ON SITE AT ALL TIMES. 3. COLLAR TIES (RINGS) IN COLUMNS DO NOT MATCH SPECIFICATIONS NOR ACI 318/340 REQUIREMENTS. 4. EXCESSIVE MORTAR FINS IN BLOCK. 5. GROUT CELLS BLOCKED WITH PAPER. 6. PREGROUT WILL NOT BE APPROVED WITHOUT SPECIAL INSPECTION REPORT ON SITE SHOWING THAT SPECIAL INSPECTOR HAS DETERMINED THAT STEEL IS IN CONFORMANCE WITH PLANS. |
|
06/12/2007 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
05/30/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* STEM WALL ONLY |