Date Description Inspector Results Comments
11/05/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/17/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CAP OFF OPEN PIPE AHEAD OF TRAP
PROVIDE A TRAP ON SECONDARY DRAIN
PROVIDE BUSHINGS IN FAN COIL REFER LINE CONNECTIONS
PROVIDE A BACKDRAFT DAMPER ON EXHAUST HOOD
OK FOR CEILING TILES