Permit: T07CM01656

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/20/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/06/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER ALL AREAS
2. NEED TO SEE CLOSET FLANGE
08/23/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
- PLAN NOT APPROVED
- A BELL REDUCER IS NOT AN INDIRECT WASTE RECEPTACLE
- DESIGN DOES NOT MEET THE STANDARD FOR A STAND PIPE RECEPTOR.
08/20/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NOT INSTALLED PER PLAN
2) PLANS DOES NOT SHOW TERMINATION OF PAIR DRAIN, T & P RELIEF DRAIN AND CONDENSATE WASTE, STAND PIPE IS NOT APPROVED RECEPTOR