Permit: T07CM01656

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01656

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
09/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PHASE I
09/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #2 & 4 FOR PHASE 1
09/24/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. EM CAN NOT WORKING
2. FINISH CIRCUIT DIRECTORIES
3. CLEAN EXCESS DIRT FROM PANELS & DISCONNECTS
4. CLOSE BOXES FROM EXPOSED WIRES AT CABINETS
5. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
6. A DISCONNECTING MEANS FOR WATER HEATER

PHASE 1 SUBJECT TO BUILDING INSPECTOR RECALL FOR 9/26/07
09/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*