Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM01656
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* 1) CONTRACTOR TO ADD MISSING EMERGENCY LIGHT OVER SOUTH SALES AREA 2) FIRE PLAN SHOWS TOTAL OF 4 DETECTORS, ONLY 1 INSTALLED AND APPROVED BY TFD |
|
11/08/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/07/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL TEMPORARY WIRING FROM CEILING 2. MC & FLEX TO BE SECURED WITHIN 12" OF TERMINATIONS AND 6' INTERVALS 3. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES 4. FINISH ALL WIRING, CLOSE OPENING IN BOXES, RACEWAYS, ETC. 5. MAKE SURE ALL FIXTURES HAVE SUPPORT WIRES, GRID SUPPORT WIRES NOT TO BE USED TO SUPPORT OTHER WIRING EQUIPMENT DO NOT CALL BEFORE COMPLETE |
|
09/24/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
09/18/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. COMPLETE ALL WIRING ABOVE CEILING - SEE ALSO PREVIOUS CORRECTIONS 2. ALL TEMP WIRING TO BE REMOVED FOR CEILING INSPECTION 3. GUTTER TO COMPLY WITH NEC 366.22 |
|
09/17/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT VDV CABLING 725.3&6, 760.3&6, 800.3&6 2. IF MANUFACTURES CLIPS ARE USED THEY MUST BE EFFECTIVE 3. FILL UNUSED OPENINGS IN BOXES 4. BOXES OVERFILLED 5. SUPPORT MC CABLE AS PER CODES 6. SUPPORT WIRES NEEDED FOR CANS FINISH ELECTRIC ABOVE CEILING |