Permit: T07CM01656

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM01656

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
1) CONTRACTOR TO ADD MISSING EMERGENCY LIGHT OVER SOUTH SALES AREA
2) FIRE PLAN SHOWS TOTAL OF 4 DETECTORS, ONLY 1 INSTALLED AND APPROVED BY TFD
11/08/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/07/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE ALL TEMPORARY WIRING FROM CEILING
2. MC & FLEX TO BE SECURED WITHIN 12" OF TERMINATIONS
AND 6' INTERVALS
3. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES
4. FINISH ALL WIRING, CLOSE OPENING IN BOXES, RACEWAYS, ETC.
5. MAKE SURE ALL FIXTURES HAVE SUPPORT WIRES, GRID SUPPORT WIRES NOT TO BE USED TO SUPPORT OTHER WIRING EQUIPMENT

DO NOT CALL BEFORE COMPLETE
09/24/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/18/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. COMPLETE ALL WIRING ABOVE CEILING - SEE ALSO PREVIOUS CORRECTIONS
2. ALL TEMP WIRING TO BE REMOVED FOR CEILING INSPECTION
3. GUTTER TO COMPLY WITH NEC 366.22
09/17/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT VDV CABLING 725.3&6, 760.3&6, 800.3&6
2. IF MANUFACTURES CLIPS ARE USED THEY MUST BE EFFECTIVE
3. FILL UNUSED OPENINGS IN BOXES
4. BOXES OVERFILLED
5. SUPPORT MC CABLE AS PER CODES
6. SUPPORT WIRES NEEDED FOR CANS

FINISH ELECTRIC ABOVE CEILING