Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01656
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
10/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PHASE II WALL COVER |
|
10/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 7 - 3/4" PVC CONDUITS IN SLAB 1. PROTECT PVC AT BASE PLATE |
|
08/22/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER PHASE ONE BASED ON APPROVAL OF REVISED PLANS. |
|
08/21/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED CORRECT, REVISED, APPROVED PLANS 2. NEED MC CONNECTORS, NOT ROMEX CONNECTORS 3. PROVIDE NAIL PLATES FOR MC AS NEEDED (HOLE LESS THAN 1 1/4" FROM STUD FACE 4. MC BEING PINCHED @ CONNECTORS 5. DO A BETTER JOB OF SECURING MC DOWN WALLS 6. TIGHTEN SET SCREWS, LOCKNUTS |
|
08/20/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) INSTALL P-RINGS & GROUND TAILS IN DEVICE BOXES, PULL WIRING FOR MAKE UP INSPECTION |
|
08/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDERGROUND BRANCH CKT/DATA RACEWAYS PHASE 1 NOTE: REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK |