Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T07CM01655
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* WATER MACHINE IS REMOVED, OWNER IS AWARE OF VIOLATION IF REINSTALLED - PIPING CAPPED |
|
02/07/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* AGREEMENT WAS REACHED THAT WATER MACHINE AT EXTERIOR BLD. NORTH OF PHARMACY WAS TO BE PROPERLY DRAINED TO INDIRECT RECEPTOR OR REMOVED, IT WAS REMOVED AND HAS BEEN REINSTALLED - PROVIDE PROOF OF CORRECT DRAIN TERMINATION OR PROVIDE IT |
|
11/28/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED IN HOUSE BACKFLOW CERTIFICATIONS FOR (7) DEVICES 2. NEED REDLINES & CITY APPROVED REVISED PLANS FOR FINAL |
|
11/20/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PROVIDE CORRECT DRAINAGE FOR GLACER WATER SYSTEM 1. PRESSURE REGULATORS ON GAS SYSTEM REQUIRE VENTS TO BE TERMINATED CORRECTLY. 2. PROVIDE BACKFLOW CERTIFICATIONS ON ALL IN HOUSE DEVICES 3. HAVE REDLINES & REVISED CITY APPROVED PLANS FOR FINAL 4. PROVIDE 1" AIR GAP FOR INDIRECT DRAINAGES AT AGUA FRESCA 5. PROVIDE CORRECT BACKFLOW PROTECTION FOR SPRAY HANDLE IN AGUA/FRESCA 6. PROVIDE CORRECT BACKFLOW PROTECTION FOR PAN WASHER SPRAYER EXCEPT ABOVE ALL AREAS OK PENDING REVISED APPROVED PLANS. |
|
11/08/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NEW HS IN DELI PER UNAPPROVED REVISION OK PROVIDE APP. PLAN REVISION GAS PSI TEST IS OK INSTALL SEDIMENT TRAPS 4" ABV ROOF PROVIDE REVISION FOR DELETION OF GAS TO OVER OK TO INSULATE HW PIPING PAINT VENT TERMINATIONS |
|
08/23/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* RESTROOM & SINK IN PHARMACY APPROVED |
|
08/22/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* PHARMACY RESTROOM OK |
|
07/27/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* RESTROOM 120 & 121 OK FOR USE PRODUCE PREP OK EXCEPT PROVIDE CORRECT (UNION-COUPLING) AT DISPOSER AND PERM CAP AT 3-COMP PREP SINK. |