Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01655
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SEAL OPEN KNOCKOUTS 2. CLOSE ALL OPEN BOXES & WIRE WAYS 3. SEAL OPENINGS IN CABINETS 4. STRAP EMT FOR ALARM SYSTEM |
|
02/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MEETING WITH SOURCE TO ADDRESS ELECTRIC VIOLATIONS. TOO MANY TO LIST - SOURCE TO GO THROUGH ENTIRE INSTALLATION & MAKE CORRECTIONS. RECALL WHEN READY AND MEET INSPECTOR ON SITE. HAVE TOOLS & LADDER TO OPEN PANEL, BOXES, ETC. 2. COMPLETE ALL ITEMS FROM 1/18 & 12/14 |
|
01/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. STRAP SEAL TIGHT PER CODE WITHIN 12" OF TERMINATIONS AND 54" BETWEEN 2. ROOFTOP UNITS HAVE PROPER FASTING 3. COMPLETE ALL OTHER ITEMS FROM PREVIOUS INSPECTIONS 4. RECALL WHEN READY |
|
12/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK PANELS X, CP 2. SOURCE TO ADDRESS REFRIGERATION PANELS, NEED TO BE NEAT & WORKMANLIKE, SEAL OPEN KNOCKOUTS, NEED TO PROPERLY STRAP EMT, CANNOT USE WHITE AS GROUND, NO SHEET METAL SCREWS FOR GROUNDING, NEED TO DERATE. HAVE MULTIPLE WIRES UNDER TERMINATIONS & STACK-ONS 3. SOURCE TO BE ON SITE FOR NEXT INSPECTION 4. STILL NEED TO SUPPORT LOW VOLTAGE CABLE ABOVE CEILING 5. STILL NEED TO ADDRESS PROPER OVERCURRENT PROTECTION FOR ROOFTOP UNITS |
|
12/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
12/12/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK LIGHTING CONTACTOR PANELS 2. OK PANELS LP, SUB-B, BP-2, R, TL 3. REFRIGERATION PANELS NEED NEW PANEL SCHEDULES. EMT TO BE STRAPPED & PANELS OPEN FOR INSPECTION 4. INSTALL LIGHT FIXTURE @ LP PANEL FOR SERVICING 5. OK EM LIGHTING EXCEPT CIRCUIT #1 & #11 6. ALARM EMT INSTALLATION AT BACK DOOR TO BE STRAPPED PER CODE 7. OK EXTERIOR OF STORE 8. REPLACE/REPAIR NON-WORKING EXITS |
|
12/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALLED AHEAD LEFT MESSAGE NO CONTRACTOR ON SITE |
|
12/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
12/06/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
12/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VIDEO & DATA CABLING TO BE SUPPORTED EVERY 6' MIN. 2. ELECTRICAL CONTRACTOR OK IN CEILING |
|
12/04/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FINAL @ AGUAS FRESCAS KIOSK 2. NEED PANEL DIRECTORY FOR BP-2 3. OK CEILING FROM AGUAS FRESCAS STORE LINE TO WEST |
|
12/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FINAL @ RESTROOMS 2. OK CEILING OUTSIDE RESTROOMS 3. OK FINAL PANEL BP 4. CHECK PROPER COLORS & PANEL SCHEDULE & PROPER BREAKERS PANEL BP-2 5. REMOVE STORAGE ITEMS FROM ELECTRIC ROOM CANNOT BE USED FOR STORAGE 6. OK FINAL PANEL D |
|
11/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINAL @ BAKERY |
|
11/16/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINALS ON PANELS P,M,M2 |
|
11/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK BRANCH CIRCUITS TO NEW WATER HEATER 2. OK FINAL AT DELI |
|
11/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/19/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
09/25/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK POWER TO RECEPTACLES AT FRONT ENTRY WALL AND FRONT WALL BY CASH REGISTERS 2. OK ROUGH FOR WALL VENDING RECEPTACLES FRONT OUTSIDE 3. OK PANEL M CUT OVER COMPLETE |
|
09/13/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK POWER TO CASH REGISTER DELI 2. OK COUNTER GFI RECEPTACLE IN DELI 3. OK WALL A4 MAIN ENTRY WAY DOORS 4. OK RECEPTACLE FOR DISPLAY LIGHTS IN COSMETICS 5. OK RECEPTACLE FOR SEASONAL DISPLAY 6. OK FLOOR BOXES IN SEASONAL 7. OK RECEPTACLE FOR LIGHTING AT GIFT WRAPPING 8. OK WIRING TO MAKE UP AIR UNIT ON ROOF |
|
08/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* BEN 955-3809 1. OK ELECTRICAL PHARMACY CLOSET LIGHT ON ORDER -- BLANKED OFF |
|
08/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PHARMACY FINAL 1. INSTALL SERVICE DISCONNECT FOR INSTANT HOT NEC 422.31 2. INSTANT HOTS INSTALLED DOES NOT MATCH WHAT PLAN CALLS FOR CIRCUIT FEEDING INSTANT HOT IS TO SMALL INSTALL PROPER SIZED CIRCUIT FOR INSTANT HOT 3. GFI RECEPT NOT WORKING/NO POWER 4. MISSING LIGHT FIXTURE IN CLOSET 5. MISSING RECEPT ON DISPLAY CASES 6. RECEPT IN ISLAND HAVE NO POWER AND MISSING MOUNTING SCREWS ON INDUSTRIAL COVERS FOR RECEPT. 7. INSTALL EXTENSION OF RECEPT MOUNTED IN WOOD PANEL AND INSTALL PLATE 8. CABINET LEG BLOCKING RECEPT 9. OK EM LIGHTS 10. OK 4 3/4" PVC IN SLAB AT DELI |
|
08/08/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK WIRING TO NEW FREEZER SECTION. PREVIOUS INSPECTION ITEMS CORRECTED 2. OK FLOOR BOX IN PRODUCE SALES 3. OK POWER IN CABINETS CUSTOMER SERVICE AREA STILL NEED CEILING INSPECTION |