Permit: T07CM01655

Parcel: 130140260


Addresses:

4150 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01655

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/25/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SEAL OPEN KNOCKOUTS
2. CLOSE ALL OPEN BOXES & WIRE WAYS
3. SEAL OPENINGS IN CABINETS
4. STRAP EMT FOR ALARM SYSTEM
02/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MEETING WITH SOURCE TO ADDRESS ELECTRIC VIOLATIONS. TOO MANY TO LIST - SOURCE TO GO THROUGH ENTIRE INSTALLATION & MAKE CORRECTIONS. RECALL WHEN READY AND MEET INSPECTOR ON SITE.
HAVE TOOLS & LADDER TO OPEN PANEL, BOXES, ETC.
2. COMPLETE ALL ITEMS FROM 1/18 & 12/14
01/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. STRAP SEAL TIGHT PER CODE WITHIN 12" OF TERMINATIONS AND 54" BETWEEN
2. ROOFTOP UNITS HAVE PROPER FASTING
3. COMPLETE ALL OTHER ITEMS FROM PREVIOUS INSPECTIONS
4. RECALL WHEN READY
12/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK PANELS X, CP
2. SOURCE TO ADDRESS REFRIGERATION PANELS, NEED TO BE NEAT & WORKMANLIKE, SEAL OPEN KNOCKOUTS, NEED TO PROPERLY STRAP EMT, CANNOT USE WHITE AS GROUND, NO SHEET METAL SCREWS FOR GROUNDING, NEED TO DERATE. HAVE MULTIPLE WIRES UNDER TERMINATIONS & STACK-ONS
3. SOURCE TO BE ON SITE FOR NEXT INSPECTION
4. STILL NEED TO SUPPORT LOW VOLTAGE CABLE ABOVE CEILING
5. STILL NEED TO ADDRESS PROPER OVERCURRENT PROTECTION FOR ROOFTOP UNITS
12/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
12/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK LIGHTING CONTACTOR PANELS
2. OK PANELS LP, SUB-B, BP-2, R, TL
3. REFRIGERATION PANELS NEED NEW PANEL SCHEDULES. EMT TO BE STRAPPED & PANELS OPEN FOR INSPECTION
4. INSTALL LIGHT FIXTURE @ LP PANEL FOR SERVICING
5. OK EM LIGHTING EXCEPT CIRCUIT #1 & #11
6. ALARM EMT INSTALLATION AT BACK DOOR TO BE STRAPPED PER CODE
7. OK EXTERIOR OF STORE
8. REPLACE/REPAIR NON-WORKING EXITS
12/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALLED AHEAD LEFT MESSAGE
NO CONTRACTOR ON SITE
12/07/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
12/06/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
12/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. VIDEO & DATA CABLING TO BE SUPPORTED EVERY 6' MIN.
2. ELECTRICAL CONTRACTOR OK IN CEILING
12/04/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK FINAL @ AGUAS FRESCAS KIOSK
2. NEED PANEL DIRECTORY FOR BP-2
3. OK CEILING FROM AGUAS FRESCAS STORE LINE TO WEST
12/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK FINAL @ RESTROOMS
2. OK CEILING OUTSIDE RESTROOMS
3. OK FINAL PANEL BP
4. CHECK PROPER COLORS & PANEL SCHEDULE & PROPER BREAKERS PANEL BP-2
5. REMOVE STORAGE ITEMS FROM ELECTRIC ROOM
CANNOT BE USED FOR STORAGE
6. OK FINAL PANEL D
11/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FINAL @ BAKERY
11/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FINALS ON PANELS P,M,M2
11/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK BRANCH CIRCUITS TO NEW WATER HEATER
2. OK FINAL AT DELI
11/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/19/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK POWER TO RECEPTACLES AT FRONT ENTRY WALL AND FRONT WALL BY CASH REGISTERS
2. OK ROUGH FOR WALL VENDING RECEPTACLES FRONT OUTSIDE
3. OK PANEL M CUT OVER COMPLETE
09/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK POWER TO CASH REGISTER DELI
2. OK COUNTER GFI RECEPTACLE IN DELI
3. OK WALL A4 MAIN ENTRY WAY DOORS
4. OK RECEPTACLE FOR DISPLAY LIGHTS IN COSMETICS
5. OK RECEPTACLE FOR SEASONAL DISPLAY
6. OK FLOOR BOXES IN SEASONAL
7. OK RECEPTACLE FOR LIGHTING AT GIFT WRAPPING
8. OK WIRING TO MAKE UP AIR UNIT ON ROOF
08/24/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
BEN 955-3809

1. OK ELECTRICAL PHARMACY
CLOSET LIGHT ON ORDER -- BLANKED OFF
08/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PHARMACY FINAL
1. INSTALL SERVICE DISCONNECT FOR INSTANT HOT
NEC 422.31
2. INSTANT HOTS INSTALLED DOES NOT MATCH WHAT PLAN CALLS FOR CIRCUIT FEEDING INSTANT HOT IS TO SMALL
INSTALL PROPER SIZED CIRCUIT FOR INSTANT HOT
3. GFI RECEPT NOT WORKING/NO POWER
4. MISSING LIGHT FIXTURE IN CLOSET
5. MISSING RECEPT ON DISPLAY CASES
6. RECEPT IN ISLAND HAVE NO POWER AND MISSING MOUNTING SCREWS ON INDUSTRIAL COVERS FOR RECEPT.
7. INSTALL EXTENSION OF RECEPT MOUNTED IN WOOD PANEL AND INSTALL PLATE
8. CABINET LEG BLOCKING RECEPT
9. OK EM LIGHTS
10. OK 4 3/4" PVC IN SLAB AT DELI
08/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK WIRING TO NEW FREEZER SECTION. PREVIOUS INSPECTION ITEMS CORRECTED
2. OK FLOOR BOX IN PRODUCE SALES
3. OK POWER IN CABINETS CUSTOMER SERVICE AREA
STILL NEED CEILING INSPECTION