Permit: T07CM01646

Parcel: 141096560

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM01646

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2007 FRAMING Approved IVRS - Inspection :*
06/25/2007 FRAMING Partial Approval IVRS - Inspection :*
06/22/2007 FRAMING Partial Approval IVRS - Inspection :*
06/21/2007 FRAMING Partial Approval IVRS - Inspection :*
06/20/2007 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) OUTSIDE METAL ELECTRIC BOX LATHED OVER
2) SEAL LATH VAPOR BARRIER
3) NO GAS PRESSURE TEST
4) PANTRY SHEARWALL REQUIRES 3 ANCHOR BOLTS
5) KITCHEN TRAP WEIR CANNOT BE HIGHER THAN VENT OPENING
6) NO DWV WATER TEST
7) NO POTABLE WATER TEST
8) ANCHOR BOLTS REQUIRED WITHIN 12" OF PLATE SPLICES
9) ROOF NOT APPROVED-CORRECT
10) STOPPED INSPECTION TOO MANY ITEMS