Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
06/27/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/26/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PRIOR INSPECTION REPORT ON SITE
2) PROVIDE ENGINEERS/SPECIAL INSPECTION REPORT FOR REPLACED HOLDOWN
06/15/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) OK TO GET READY FOR STUCCO MESH, WILL BE ABLE TO RE-INSPECT AT INTERMEDIATE
2) RETRO NOT IN PLACE-UNABLE TO GET REQUIRED DEPTH ON ANCHOR BOLT TO RETRO DUE TO SOMETHING (REBAR) IN FOOTER SLAB. NEED TO GET ENGINEER APPROVAL AS TO WERE TO LOCATE HOLDOWN. WILL NEED ENGINEER RELOCATIONS
06/12/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Holdowns require .162 x 3 1/2" nails commons 2 1/2" nails used
Nails for holdowns must nail into studs
S.E. shearwall north holdown wrong location-repeat
Refee
06/11/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOLDOWNS NOT NAILED INTO STUDS
2) S.E. HOLDOWN WRONG LOCATION-PROVIDE RETRO
3) S. SHEARWALL NOT 10 FT LONG
4) WEDGE ANCHORS NOT ALLOWED ON EXTERIOR SHEARWALLS
5) SEE ITEMS 1,2,3,4,5 & 10 FROM 6/5/07
06/05/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PAHD 42 HOLDOWNS REQUIRE 3 1/2" X .162 NAILS PRESENTLY 3" X .131-REPLACE NAILS IN ALL HOLDOWNS
2) S.E. CORNER NORTH HOLDOWN IN WRONG LOCATION. PROVIDE ENGINEERS APPROVED ? IN CORRECT LOCATION
3) SOUTH #9 SHEARWALL MUT BE 10 FT LONG MINIMUM
4) WEDGE ANCHORS NOT ALLOWED ON FIRST FLOOR SHEAR EXTERIOR WALLS-MUST USE TAP CONS OR EQUAL. REMOVE NUTS FROM WEDGE
5) SECOND FLOOR SILL PLATE NOT SUPPORTED ON FLOOR SHEATHING
6) ENTRY REQUIRES 1 TRIMMER 2 KING STUDS
7) STAIR GIRDER REQUIRES 2-2 X POSTS 2 LOCATIONS
8) REPLACE DAMAGED HANGER AT STAIRS
9) EAST END OF STAIR HEADER MUST BEAR ON POST NOT HANGER
10) PROVIDE DETAIL FOR STAIR HEADER WEST END WHEN OPEN WEBB TRUSS USED TWO LOCATIONS