Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01643
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED GFI TEST REPORT OK FINAL |
|
02/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SERVICE INSTALLATION ONLY 2) RECEIVED LETTER FOR TORQUE |
|
01/31/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION |
|
01/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LETTER OF TORQUE. CHECK BUSSING TORQUED PROPERLY 2. NEED TO PERFORM GFI TEST ON MAIN SERVICE DISCONNECT 3. SECURE SWITCH BOARD TO GROUND 4. MARK SERVICE CORRECTLY 5. NEED TO PROVIDE SERVICE CONDUCTOR SITE 6. INSTALL BELL ENDS ON PVC ENTRANCE/OR PROTECTIVE BUSHING 7. INSTALL COVER ON OPEN GUTTER 8. INSTALL MISSING COVER ON SECTION 2 9. INSTALL LOCK WASHERS PROPERLY |