Inspection History Details
Inspection Status: Denied
Inspection History: ENGINEERING - FINAL
Permit Number - T07CM01639
Inspection Description - ENGINEERING - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2008 | ENGINEERING - FINAL | Denied | NO PLANS ON SITE CONTRACTOR WILL RECALL |
|
10/08/2008 | ENGINEERING - FINAL | Approved | -CONTRACTOR PROVIDED PLAN SETS AND REVISED STAMPED DRAWING (8 1/2" X 11" STAMPED 8/21/08) -PICTURES TO SHOW INSTALLATION-NO SCALE/REFERENCE IN PICTURE -NO SETTLING IN WHAT APPEARS TO BE DISTURBED AREA -REVISION TO BE ADDED TO AS-BUILTS FOR COT RECORDS |
|
09/05/2008 | ENGINEERING - FINAL | Denied | PEE GRAVEL RAINWATER DRAINAGE PIT DOES NOT MEET THE REVISED, APPROVED SKETCH R-9 DATED 8/20/08. THE PIT IS LOCATED APPROXIMATELY 5 FEET AND 5.5 FEET RESPECTIVELY FROM THE NEW BLDG FOUNDATION AND SIDEWALK. THE APPROVED SKETCH CALLS FOR A DISTANCE OF 10 FEET MINIMUM FROM BOTH. IN ADDITION , ADDRESS DIFFERENTIAL SETTLEMENT OF PIT |
|
09/03/2008 | ENGINEERING - FINAL | Denied | REVISED ROOF DRAINAGE SUMP (GRAVEL PIT) HAS SETTLED AND HAS CAUSED A POTENTIAL SAFETY HAZARD. | |
08/05/2008 | ENGINEERING - FINAL | Partial Approval | PROVIDE REVISED DRAWING AND/OR DETAIL SHOWING CHANGE TO PLAN FOR ROOF DRAIN TERMINATION POINT IN COURTYARD. CHANGE MUST BE APPROVED BY COT REVIEW ENGINEER. OK FOR TEMP ONLY |