Permit: T07CM01639


Addresses:

1300 E 6TH ST


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T07CM01639

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/04/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
06/27/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SECOND FLOOR INTERMEDIATE OK
OK TO INSTALL CEILING TILES
SECOND FLOOR HYDRONIC TEST ON RTU'S OK
04/29/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
ISOLATORS ON UNITS OK
BRANCH TAPS OK
FLUE PIPE OK
PROVIDE DUCTMATE CLIPS
OK TO WRAP SPIRAL PIPING
04/22/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SECOND FLOOR OK TO PROCEED FLUE OK
04/18/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEAL ALL SCREWS IN DOUBLE WALL PIPE WITH APPROVED RTU SEALANT
CALL FOR REINSPECTION NO TAPE
04/16/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE DUCTMATE CLIPS @ OSA FAN
2. REMOVE SHEETROCK TO INSPECT FLUE PIPING
3. PROVIDE BRANCH TAPS PER PLANS
4. PROVIDE & INSTALL ISOLATORS PER PLANS